← All playbooks
CriticalExploited vuln · 2026-11-25

Danfoss AK-SM 800A CVE-2023-25914, CVE-2023-25915 and CVE-2025-41450: path traversal, command execution and auth bypass exploited (CISA KEV)

SockAnalyst · by Mario Velasco Jr., CompTIA Security+ CE

⚡ Triage: do you need this playbook?

If any row below is true in your environment, work this playbook. Start at the row that matches.

If you see this…Look hereIt meansDo this
AK-SM 800A software below 3.3Controller web UI versionExposed to CVE-2023-25914/25915 (KEV)Install patch 3.3+
Software below 4.2 / R4.2Controller web UI versionExposed to CVE-2025-41450 auth bypass (KEV)Install patch 4.2+
Controller reachable from the internetExposure scan / firewall rulesDirectly exploitableRemove from the internet
Web UI access from outside your management networksProxy / firewall logsPossible exploitationRun the IR branch
Severity: CriticalCISA KEV: 3 CVEs listedEPSS: CVE-2025-41450 0.05 · CVE-2023-25915 0.03 · CVE-2023-25914 0.02 (2026-11-28)Vendor advisory: DSA-2023-08-01 and DSA-2025-03-01Vendor-published IOCs: none publishedLast verified against vendor: 2026-11-28

EPSS is FIRST.org's estimated chance of exploitation in the next 30 days; CISA KEV status (confirmed exploitation) is the stronger signal. Which playbook do I need? See every signal →

🧭 Are you affected? Quick exposure check

  • Do your sites (stores, cold rooms) use Danfoss AK-SM 800A controllers?
  • Who manages them (often an outside refrigeration contractor)?
  • Are they on the internet?

What happened

On August 21, 2023 Danfoss published security advisory DSA-2023-08-01 for the AK-SM 800A Series system manager, a refrigeration and building-management controller. The advisory covers three flaws in software below version 3.3: CVE-2023-25913, an authentication bypass that can expose a sensitive web report (not currently in CISA's KEV catalog); CVE-2023-25914, a path traversal through the XML interface that lets an attacker read system files on the underlying server, which NVD says can lead to a full system compromise (NVD CVSS 8.8 High; Danfoss scored it 7.5 High); and CVE-2023-25915, improper input validation that lets a remote attacker execute commands (Danfoss 9.8 Critical; NVD 8.8 High). NVD and the Dutch Institute for Vulnerability Disclosure (DIVD-2023-00025) describe the 2023 path-traversal and command-execution flaws as requiring authentication; CISA's KEV short descriptions do not state a privilege requirement. Danfoss credits HackDefense, Synacktiv and DIVD. On March 24, 2025 Danfoss published DSA-2025-03-01 for CVE-2025-41450, a later authentication issue in the same product family: the web interface generated predictable passwords from date and time, and a web report could leak IP addresses, usernames and store names. NVD says that issue affects the series prior to version 4.2 (NVD CVSS 7.5 High). CISA ICS advisory ICSA-25-140-03, revised November 18, 2026, still said CISA was not aware of public exploitation of the 2025 issues at that writing. On November 25, 2026 CISA added CVE-2023-25914, CVE-2023-25915 and CVE-2025-41450 to the Known Exploited Vulnerabilities catalog, with federal due dates of November 28, 2026 for the 2023 flaws (forensic triage required) and December 9, 2026 for CVE-2025-41450 (forensic triage not required). Known ransomware campaign use is listed as Unknown. The same 2025 advisory and ICS write-up also cover CVE-2025-41451 and CVE-2025-41452, fixed in 4.3.1; those two are not in the KEV catalog. No indicators of compromise were published in the Danfoss, CISA or DIVD notices we reviewed.

Who's affected

Operators of Danfoss AK-SM 800A Series system managers, commonly used in commercial-facility refrigeration and building controls. Software below 3.3 is still exposed to CVE-2023-25914 and CVE-2023-25915 (and the related, non-KEV CVE-2023-25913). Software prior to 4.2 / R4.2 is exposed to CVE-2025-41450. Controllers whose web UI or XML interface is reachable from the internet or from untrusted networks are at highest risk.

✅ Fix / patch

  • Inventory every AK-SM 800A Series controller and record the software version.
  • For CVE-2023-25914 and CVE-2023-25915 (and related CVE-2023-25913): install software version 3.3 or later, as Danfoss specifies in DSA-2023-08-01.
  • For CVE-2025-41450: install software version 4.2 or R4.2 or later, as Danfoss specifies in DSA-2025-03-01. Do not stop at 3.3 if you also need the 2025 fix. Consider 4.3.1 if you want the additional non-KEV fixes (CVE-2025-41451 and CVE-2025-41452) shipped in that later advisory.
  • Remove the controllers from the public internet. Restrict the web UI and XML interface to a management network, and require a VPN or equivalent when remote access is needed, consistent with CISA's ICS practice for these products.
  • Federal agencies: meet the KEV due dates — November 28, 2026 for CVE-2023-25914 and CVE-2023-25915, and December 9, 2026 for CVE-2025-41450. Complete forensic triage under BOD 26-04 for the two 2023 KEV CVEs (required); forensic triage is not required for CVE-2025-41450.
  • After a suspected compromise, isolate the controller and review web, reverse-proxy and firewall logs of access to the management interface before returning a patched unit to service. Danfoss has not published IOCs.

🚨 Compromised already? Do this

Run this if a red triage row is true or the persistence check finds anything.

  1. Install patch 3.3 or later for CVE-2023-25914/25915. Vendor advisory
  2. Install patch 4.2 or later for CVE-2025-41450. Vendor advisory
  3. Restrict the web UI to a management network or VPN. SockAnalyst mapping

🧰 Vendor tools and logs to collect

Logs to collect and keep:

  • Firewall / reverse proxy logs in front of controllers.

🔎 Quick hunt check

No IOCs (IPs, domains, hashes) or exploit request paths have been published by Danfoss, CISA or DIVD. These are industrial controllers; an EDR sensor is often not installed on the appliance itself. Hunt in web, reverse-proxy and firewall logs that see the AK-SM 800A management interface: (1) access to inventoried controller addresses from the internet or from any network that is not your management/VPN path — unexpected exposure is itself a finding; (2) new or high-volume XML or other API POSTs to those hosts, especially around authentication or report generation; (3) after possible command execution (CVE-2023-25915), unusual outbound connections originating from the controller. Replace YOUR_AKSM_IPS / YOUR_AKSM_HOSTS and YOUR_MGMT_NETS in the queries with your inventory. Defender XDR and CrowdStrike will not see web URIs unless you also ingest proxy or firewall logs — those tabs hunt network connections to and from the controllers instead.

MITRE ATT&CK: T1190, T1059, T1005

IOCs

No IOCs (IPs, domains or hashes) published by the sources yet.

Hunt queries

Hunt logic (works with any SIEM)

Plain-English version of the hunt for teams on homegrown or other SIEM/SOAR tools. The tabs below implement the same logic.

Data source
Web proxy logs; Firewall or network-flow logs.
What to look for
  • Hunts access to inventoried Danfoss AK-SM 800A controller addresses from outside the management path. Replace the dst_ip CIDR with your controller inventory and the source allow-list with your management or VPN networks. For CVE-2023-25914, CVE-2023-25915 and CVE-2025-41450.
  • After possible command execution (CVE-2023-25915), hunt unexpected outbound connections whose source is an inventoried AK-SM 800A controller. Replace the source CIDR with your inventory. 203.0.113.0/24 is documentation-only until edited.
Key fields
destination IP, source IP, destination port
IOCs
No IOCs published by Danfoss, CISA or DIVD as of Nov 27, 2026. CISA has not described the exploitation it observed.
False positives
Your own management stations, vendor service access or monitoring systems reaching the controllers match until you add them to the allow-list. Controllers also make legitimate outbound calls (time sync, DNS, vendor or monitoring services); tune the allowed ports and destinations to your baseline.

These queries are starting points built only from published indicators. Field names and log sources differ in every environment, so test and tune them before you rely on them.

# Needs proxy, web or firewall logs. Replace the destination addresses with inventoried AK-SM 800A IPs before use. 203.0.113.0/24 is documentation-only (RFC 5737) and will not match production traffic until you edit it. No published IOCs.
title: Unexpected web or proxy access to Danfoss AK-SM 800A management interfaces
id: 8f119dbc-93ba-4ec7-9774-73af062d7f00
status: experimental
description: Hunts access to inventoried Danfoss AK-SM 800A controller addresses from outside the management path. Replace the dst_ip CIDR with your controller inventory and the source allow-list with your management or VPN networks. For CVE-2023-25914, CVE-2023-25915 and CVE-2025-41450.
references:
  - https://www.danfoss.com/en/service-and-support/coordinated-vulnerability-disclosure/danfoss-security-advisories/dsa-2023-08-01/
  - https://www.danfoss.com/en/service-and-support/coordinated-vulnerability-disclosure/danfoss-security-advisories/dsa-2025-03-01/
  - https://www.cisa.gov/news-events/alerts/2026/11/25/cisa-adds-10-known-exploited-vulnerabilities-catalog
  - https://www.cisa.gov/news-events/ics-advisories/icsa-25-140-03
  - https://csirt.divd.nl/DIVD-2023-00025/
  - https://sockanalyst.com/patch-now/danfoss-ak-sm-800a-cve-2023-25914-cve-2023-25915-cve-2025-41450-exploited-kev
author: SockAnalyst
date: 2026-11-25
tags:
  - attack.t1190
  - attack.t1059
  - attack.t1005
logsource:
  category: proxy
detection:
  selection:
    dst_ip|cidr:
      - 203.0.113.0/24
  filter_mgmt:
    src_ip|cidr:
      - 10.0.0.0/8
      - 172.16.0.0/12
      - 192.168.0.0/16
  condition: selection and not filter_mgmt
falsepositives:
  - Legitimate management, vendor or monitoring access not yet added to the allow-list
level: high
---
title: Outbound connections originating from Danfoss AK-SM 800A controllers
id: 3fd0e1c4-52dc-4467-8645-00b59579028f
status: experimental
description: After possible command execution (CVE-2023-25915), hunt unexpected outbound connections whose source is an inventoried AK-SM 800A controller. Replace the source CIDR with your inventory. 203.0.113.0/24 is documentation-only until edited.
references:
  - https://www.danfoss.com/en/service-and-support/coordinated-vulnerability-disclosure/danfoss-security-advisories/dsa-2023-08-01/
  - https://www.cisa.gov/news-events/alerts/2026/11/25/cisa-adds-10-known-exploited-vulnerabilities-catalog
  - https://sockanalyst.com/patch-now/danfoss-ak-sm-800a-cve-2023-25914-cve-2023-25915-cve-2025-41450-exploited-kev
author: SockAnalyst
date: 2026-11-25
tags:
  - attack.t1190
  - attack.t1059
  - attack.t1005
logsource:
  category: firewall
detection:
  selection:
    src_ip|cidr:
      - 203.0.113.0/24
  filter_expected:
    dst_port:
      - 123
      - 53
  condition: selection and not filter_expected
falsepositives:
  - Legitimate controller callbacks, time sync, DNS, vendor update or monitoring traffic; tune ports and destinations to your baseline
level: high
```Danfoss AK-SM 800A: unexpected access to inventoried controller management interfaces```
# Needs web, reverse-proxy or firewall logs that include the AK-SM 800A web UI. Replace YOUR_AKSM_IPS / YOUR_AKSM_HOSTS with inventoried controller addresses and YOUR_MGMT_NETS with the management or VPN path that should be talking to them. Danfoss and CISA have not published exploit paths or IOCs.
index=* earliest=11/01/2026:00:00:00
(dest_ip IN (YOUR_AKSM_IPS) OR dest IN (YOUR_AKSM_HOSTS) OR dest_nt_host IN (YOUR_AKSM_HOSTS))
| eval src=coalesce(src_ip, src, clientip, c_ip, "")
| eval dest=coalesce(dest_ip, dest, dest_nt_host, "")
| eval uri=coalesce(uri_path, uri, url, cs_uri_stem, http_uri, "")
| eval method=coalesce(method, http_method, cs_method, "")
| eval status=coalesce(status, http_status, status_code, sc_status, "")
| eval src_is_mgmt=if(cidrmatch("YOUR_MGMT_NETS", src), 1, 0)
| eval signal=case(
    src_is_mgmt=0, "non_mgmt_access_to_aksm",
    match(method,"(?i)POST") AND match(uri,"(?i)xml|report|login|auth"), "xml_or_auth_post_to_aksm",
    match(method,"(?i)POST"), "post_to_aksm",
    1=1, "aksm_access")
| stats count min(_time) as first max(_time) as last values(method) as methods values(uri) as uris values(status) as statuses values(signal) as signals by src, dest
| sort -count
// Danfoss AK-SM 800A: unexpected access to inventoried controller management interfaces. Needs web, proxy or firewall logs (CommonSecurityLog / W3CIISLog / equivalent). Replace the IP lists. Danfoss and CISA have not published exploit paths or IOCs.
let Since = datetime(2026-11-01);
let AksmIps = dynamic(["YOUR_AKSM_IPS"]);
let MgmtNets = dynamic(["YOUR_MGMT_NETS"]);
union isfuzzy=true
(CommonSecurityLog | where TimeGenerated >= Since
 | extend src=coalesce(SourceIP, SourceTranslatedAddress, ""), dest=coalesce(DestinationIP, DestinationTranslatedAddress, ""), uri=coalesce(RequestURL, RequestContext, ""), method=RequestMethod, status=tostring(ResultCode)
 | where dest has_any (AksmIps) or DestinationHostName has_any (dynamic(["YOUR_AKSM_HOSTS"]))),
(W3CIISLog | where TimeGenerated >= Since
 | extend src=cIP, dest=coalesce(sIP, Computer, ""), uri=csUriStem, method=csMethod, status=tostring(scStatus)
 | where dest has_any (AksmIps) or Computer has_any (dynamic(["YOUR_AKSM_HOSTS"])))
| extend src_is_mgmt = ipv4_is_in_range(src, "YOUR_MGMT_NETS")
| extend signal = case(
    src_is_mgmt == false, "non_mgmt_access_to_aksm",
    method has_any ("POST") and uri has_any ("xml","report","login","auth"), "xml_or_auth_post_to_aksm",
    method has_any ("POST"), "post_to_aksm",
    "aksm_access")
| summarize count(), first=min(TimeGenerated), last=max(TimeGenerated), methods=make_set(method), uris=make_set(uri), signals=make_set(signal) by src, dest
| sort by count_ desc
// AK-SM 800A appliances typically have no Defender sensor. This hunts DeviceNetworkEvents to or from inventoried controller IPs. Web URIs and XML bodies are not in Defender XDR — use the Splunk or Sentinel tabs against proxy/firewall logs. Replace the IP lists. No published IOCs.
let Since = datetime(2026-11-01);
let AksmIps = dynamic(["YOUR_AKSM_IPS"]);
DeviceNetworkEvents
| where Timestamp >= Since
| where RemoteIP in (AksmIps) or LocalIP in (AksmIps)
| extend direction = case(RemoteIP in (AksmIps), "to_aksm", "from_aksm")
| extend other = iff(direction == "to_aksm", InitiatingProcessCommandLine, RemoteIP)
| summarize count(), first=min(Timestamp), last=max(Timestamp), ports=make_set(RemotePort), actions=make_set(ActionType), devices=make_set(DeviceName) by direction, LocalIP, RemoteIP, RemoteUrl
| sort by count_ desc
// Elastic EQL. Unexpected access to inventoried AK-SM 800A management interfaces (web, proxy or firewall logs). Replace YOUR_AKSM_IPS. No published IOCs.
any where @timestamp >= "2026-11-01T00:00:00Z" and (
  destination.ip : ("YOUR_AKSM_IPS") or source.ip : ("YOUR_AKSM_IPS")
)
// Falcon LogScale (CQL). Network connections to or from inventoried AK-SM 800A IPs. Web URIs need ingested proxy or firewall logs (see the Splunk/Sentinel tabs). Set the time range from Nov 1, 2026. Replace YOUR_AKSM_IPS. No published IOCs.
(#event_simpleName=NetworkConnectIP4 or #event_simpleName=NetworkConnectIP6 or #event_simpleName=NetworkReceiveAcceptIP4)
and (RemoteAddressIP4=/YOUR_AKSM_IPS/ or LocalAddressIP4=/YOUR_AKSM_IPS/)

Sigma rule checked with pySigma 1.5.1 and the SigmaHQ validators; it converts with the official Splunk, Kusto (KQL), Elastic EQL, Elastic Lucene, Elastic ES|QL backends (not CrowdStrike LogScale: backend limitation). The platform tabs are hand-written versions of the same hunt, not raw conversions. None of these queries has been run against live data.

For educational and informational purposes only. Hunt queries and detection rules are provided as-is, without warranty, and have not been tested against your environment or live data. Review, test and tune them in a non-production setting before use. SockAnalyst is not responsible for any outcome of using this content. Always follow your organization's policies and the vendor's official guidance. Zero Trust applies here too: never trust, always verify.

See all hunt queries →

⏱ CISA deadline

CVE-2023-25914CVSS 8.8 High (v3.1, NVD)
--
Federal due 2026-11-28 · CISA KEV catalog
CVE-2023-25915CVSS 8.8 High (v3.1, NVD)
--
Federal due 2026-11-28 · CISA KEV catalog
CVE-2025-41450CVSS 7.5 High (v3.1, NVD)
--
Federal due 2026-12-09 · CISA KEV catalog

Sources

Vendor advisories (primary)

Government and CERT

Press and other reporting

Vendor facts on this page (fixed builds, remediation, tools, indicators) were checked against the vendor and government pages above on 2026-11-28.

Related playbooks

Get the SockAnalyst Weekly Brief free, every Thursday.

One email a week with the KEV deadlines, patches and hunt queries that matter. New playbooks still post here on the site every morning.

Subscribe free

Read the free weekly pack →